home *** CD-ROM | disk | FTP | other *** search
/ ASME's Mechanical Engine…ing Toolkit 1997 December / ASME's Mechanical Engineering Toolkit 1997 December.iso / hvac / civano.txt < prev    next >
Text File  |  1996-01-01  |  30KB  |  694 lines

  1.                                          Exhibit A
  2.                                          Ordinance Number ________
  3.  
  4.  
  5.                         CIVANO ENERGY CODE
  6.  
  7.  
  8. FINAL DRAFT   -              10/26/95
  9.  
  10.  
  11.     (CABO Model Energy Code, 1995 Edition Modified for Civano)
  12. Material to be added is shown; material to be deleted is shown as 
  13. *>strikeout<* .
  14.  
  15.                             CHAPTER 1
  16.                   ADMINISTRATION AND ENFORCEMENT
  17.  
  18. Section 101.4  Scope.  Add a paragraph to read:
  19. The calculated source annual energy consumption at the building
  20. site shall be less than the energy required by the present
  21. Tucson/Pima County Model Energy Code by the following percentages:
  22.  
  23. Single family/Multifamily dwellings -             60 percent
  24. Commercial buildings/Retail Establishments -      50 percent
  25.  
  26. Source energy consumption shall be determined by multiplying the
  27. site energy usage in KBtuh per square foot by the following
  28. factors:
  29.  
  30.   Site Energy                                     Factor
  31.  
  32.   Electric                                        3.10
  33.   Gas                                             1.11
  34.   Wood                                            1.00
  35.   Solar (amount of displaced electric or gas)     0.00
  36.  
  37. Section 102.2 Maintenance Information:  Delete the first two
  38. sentences.
  39.  
  40. Section 102.3 Change the first sentence to read:  Whole-window U-factor, solar heat gain coefficient, visible light transmittance
  41. and air leakage values of fenestration products ...
  42.  
  43. Table 102.3a  Add the following notes at the end of the table:
  44. The minimum design characteristics to qualify as a Thermal Break
  45. are:
  46.  
  47.   a.  The material used as the thermal break must have a thermal
  48. conductivity of not more than 3.6 Btu/inch/hr/sq. ft./oF, and;
  49.   b.  The thermal break must produce a gap not less than 0.210
  50. inches, and;
  51.   c.  All metal members of the product exposed to interior and
  52. exterior air must incorporate a thermal break meeting the criteria
  53. in (a) and (b) above.
  54.  
  55. In addition, the product must be clearly labeled by the
  56. manufacturer that it qualifies as a thermally broken product.
  57.  Non-metal products may include metal fasteners, hardware, and door
  58. thresholds.
  59.  For all dual glazed products, adjust the listed U-values as
  60. follows:
  61.  
  62.   a.  Subtract 0.05 for spacers 7/16" or wider.
  63.   b.  Add 0.05 for products with dividers between panes if the
  64. spacer is less than 7/16" wide.
  65.   c.  Add 0.05 to any product with true divided lites (dividers
  66. through the panes).
  67.  
  68. Section 102.4  Equipment  Add a new subsection to read:
  69.  
  70. 102.4  Equipment.  Buildings constructed under the provisions of
  71. this code shall be permitted to use refrigerated air conditioning
  72. systems only if installed in conjunction with ductwork, electrical
  73. service and control wiring and plumbing compatible with an
  74. evaporative cooler.  Other provisions of this code notwithstanding,
  75. air conditioning equipment shall have a minimum SEER of 12 or a
  76. minimum EER of 10.
  77.  
  78. Section 104.1 General:  Delete parenthesis around last sentence,
  79. delete the Footnote.
  80. Add a paragraph after the exception to read:
  81. Plans and specifications shall show the method of utilizing solar
  82. energy.  Solar usage shall include, but not be limited to, optimum
  83. building orientation, passive solar design for window placement,
  84. solar water heating or space heating.
  85.  
  86.  
  87.                             CHAPTER 2
  88.                            DEFINITIONS
  89.  
  90. Section 201  Definitions: Revise as follows:
  91.  
  92. 201.1  Application of Terms.  Conditioned Floor Area:  
  93. Delete the words "The horizontal projection of", and capitalize the
  94. new first word "That".
  95.  
  96. 201.1 Application of Terms.  Positive Cooling Supply:  
  97. Insert including evaporative cooling systems, between "cooling" and
  98. "deliberately"  
  99.  
  100. Add a new subsection:
  101.  
  102. 201.1 Application of Terms.  Civano:   A Tucson Solar Village,  a
  103. model sustainable community;  a vision of the future where resource
  104. consumption is reduced through more efficient technologies, use of
  105. solar energy and lifestyles which promote greater harmony and
  106. balance with the natural environment;  a community in the spirit of
  107. the "Civano" period, a golden era of the Hohokam culture which
  108. balanced natural resources and human needs;   incorporates and
  109. demonstrates strategies for achieving more sustainable development.
  110.  
  111. Add a new subsection:
  112.  
  113. 201.1 Application of Terms.  Power Density:   The total connected
  114. power load of all components of a building system, including all
  115. auxiliary components and circuitry, without regard to the timing,
  116. scheduling, or control of their operation, in w/ft2 or Btuh/ft2.
  117. Add a new subsection:
  118.  
  119. 201.1  Application of Terms.  Site Energy:  Energy, other than
  120. recovered energy, utilized for any purpose on the site.
  121.  
  122. 201.1  Application of Terms.  SOLAR ENERGY SOURCE.  Revise to read:
  123.  
  124. SOLAR ENERGY SOURCE.   *>Source of n<*  Natural daylighting  *>and
  125. of<*  or thermal, chemical or electrical energy derived directly
  126. from conversion of incident solar radiation.
  127.  
  128. 201.1 Application of Terms.  Water-chilling Package of Absorption
  129. Revise to read:  
  130. Water-chilling package, absorption.
  131.  
  132.                             CHAPTER 3
  133.                         DESIGN CONDITIONS
  134. Table 302.1  
  135. Exterior design conditions:  Revise the table as follows:
  136.  
  137.  
  138.                                     Table 302.1 
  139.                        Exterior Design Conditions3
  140.  
  141.  
  142.    WINTER  DESIGN DRY BULB TEMP.         30 oF
  143.    SUMMER  DESIGN DRY BULB TEMP.        104 oF
  144.            DESIGN WET BULB TEMP.        66 oF
  145.    DEGREE DAYS HEATING                   7000
  146.    DEGREES NORTH LATITUDE                32o
  147.  
  148. 3 This table is not intended to be used for the purpose of system
  149. or equipment sizing.
  150.  
  151. Add a new section to read:
  152.  
  153.                            SECTION 304
  154.                WOOD-BURNING STOVES AND FIREPLACES 
  155.  
  156. 304.1  General.  A wood-burning stove or fireplace shall be
  157. considered as providing the required space heating energy only when
  158. installed as backup energy for a solar-thermal collection system.
  159.  
  160. 304.2  Wood-burning stoves.  Wood-burning stoves shall be labeled
  161. to show compliance with the following U. S. Environmental
  162. Protection Agency (EPA) standards for particulate emissions during
  163. operation:
  164.  
  165. Stoves with catalytic elements      4.1 grams per hour
  166. Stoves without catalytic elements   7.5 grams per hour
  167.  
  168. Catalytic stoves shall have an accessible, modular, replaceable
  169. catalyst element.
  170.  
  171. 304.3  Fireplaces.  Wood-burning fireplaces shall be provided with
  172. a means of supplying 100% of the combustion air for operation from
  173. the outside, and shall limit particulate emissions to less than 7.5
  174. grams per hour.  All fireplaces shall be provided with a tight
  175. fitting glass door and a positive means of circulating the heated
  176. air in the occupied space.
  177.  
  178.                            CHAPTER 4
  179.          RESIDENTIAL BUILDING DESIGN BY SYSTEMS ANALYSIS
  180.                 AND DESIGN OF BUILDINGS UTILIZING
  181.                      RENEWABLE ENERGY SOURCES
  182.  
  183. Section 402.1  Energy Analysis.  Change the first paragraph to
  184. read:  
  185.  
  186. 402.1  Energy Analysis.  Compliance with this chapter will require
  187. an analysis of the annual source energy usage as required in
  188. section 101.4, hereinafter called an annual energy analysis.
  189.  
  190. 402.1.1  Input values for Group R buildings.  Add a sentence at the
  191. end of the first paragraph to read:
  192. Domestic hot water energy use must be calculated separately from
  193. glazing systems, heat storage, thermal envelope and space
  194. conditioning equipment and must meet the energy reduction
  195. percentages of section 101.4.
  196.  
  197. Distribution System Loss Factor on page 12;  change the Outside
  198. factor for Cooling to read  *>0.80 <*  0.75.
  199.  
  200. Section 402.4 Calculation Procedure.  
  201. Operational Characteristics:  Add a sentence to read:
  202. The occupied mode shall be not less than 10 hours in a 24-hour
  203. period.
  204.  
  205. Section 402.5  Documentation.  Delete the exception.
  206.  
  207. Section 404.1  Water heaters, storage tanks and boilers.  Add a
  208. sentence to read:
  209. All water heating applications which exceed a 30oF  T shall include
  210. a solar heating component, heat recovery from a device other than
  211. the water heater or an energy-equivalent alternative on a fuel use
  212. basis.
  213.  
  214.                             CHAPTER 5
  215.              RESIDENTIAL BUILDING DESIGN BY COMPONENT
  216.                        PERFORMANCE APPROACH
  217.  
  218. Section 502.1 General:  Add:
  219. Thermal design parameters to be used in this chapter are found in
  220. Chapter 3, Section 302.1.
  221.  
  222. Section 502.1.2:  Revise the second paragraph by placing a comma
  223. after "Masonry", and adding "earthen materials," between "Masonry"
  224. and "or".
  225.  
  226. Table No. 502.1.2c  Delete the phrase " *>, SUCH AS A LOGWALL<* "
  227. in the heading. 
  228.  
  229. Section 502.2.1  Walls.  Add a subsection to read:
  230.  
  231. 502.2.1.2  Glazing.  Whole-unit glazing maximum U-value shall be
  232. determined by the following equation:
  233.  
  234.      U =                5               
  235.             (Glazing Percentage) - 5
  236.  
  237. where Glazing Percentage = 100 x (glazing area  /  floor area)
  238.  
  239. Table 502.2.1a  Revise as follows:
  240.                                  
  241. Table 502.2.1a ( 1 )
  242.  
  243.  
  244.  
  245.                    HEATING AND COOLING CRITERIA
  246.  
  247. ELEMENT                  MODE           TYPE A-1 BUILDINGS
  248.                                          or TYPE A-2   BUILDINGS
  249.  
  250.                                         UO
  251.  
  252. Walls   *>2 <*      Heating or cooling  0.110
  253. Roof/Ceiling        Heating or cooling  0.026
  254. Floors over unheated spaces
  255.                     Heating or cooling  0.05
  256. Heated slab on grade  *>3<*   
  257.                     Heating             R-Value  5
  258. Unheated slab on grade  *> 4<* 
  259.                     Heating             R-Value  5
  260. Basement wall  *>5<*  2  
  261.                     Heating or cooling  U-Value  0.095
  262. Crawl space wall  *>5,6<*  2,3
  263.                     Heating or cooling  U-Value  0.06
  264.  
  265. 1 Values  *>shall be<*  are determined by using the graphs (Figure
  266. Nos. 1, 2, 3, 4, 5 and 6) contained in Chapter 8 using heating
  267. degree days as specified in Section 302.
  268.  *>2 Walls.  The requirements for locations with less than 500
  269. heating degree days shall be:
  270. (a) No maximum Uo if building is heated only.
  271. (b) If the building is to be mechanically cooled when built or if
  272. provision is made for the future addition of mechanical cooling,
  273. the maximum Uo for walls in Type A-1 buildings shall be 0.30
  274. Btuh/ft/oF and in type A-2 buildings shall be 0.38 Btuh/ft/oF.<*  
  275.  *>3<*   *>There are no insulation requirements for heated slabs in
  276. locations having less than 500 Fahrenheit heating degree days.
  277. 4 There are no insulation requirements for unheated slabs in
  278. locations having less than 2,500 Fahrenheit heating degreedays.<* 
  279.  *>5<*  2 Basement and crawl space wall U values shall be based on
  280. the wall components and surface air films.  Adjacent soil shall not
  281. be considered in the determination of the U value.
  282.  *>6<*  3 Typical foundation wall insulation techniques can be
  283. found in Standard RS-20 listed in Chapter 8.
  284.  
  285. Section 502.2.2 Roof/ceiling.  Add the following:
  286. Roof/ceiling surfaces shall have a Heat Rejection Index greater
  287. than 0.8 over at least 75 percent of the opaque area, as determined
  288. by the formula
  289.  
  290. Heat Rejection Index = albedo + (absorptance x emissivity) / 2
  291.  
  292. where:
  293.  
  294. albedo = the portion of light across visible spectrum reflected, 
  295.              on a 0 to 1 scale
  296.  
  297. absorptance = 1 - reflectance
  298.  
  299. emissivity = portion of absorbed heat radiantly emitted, across the
  300. infrared spectrum, on a 0 to 1 scale as determined for varying
  301. finishes by Standard RS-56, listed in Chapter 8,or other
  302. documentation approved by the building official. 
  303.  
  304. Section 502.2.4 Slab-on-grade floors:  Revise as follows:
  305.  
  306. 502.2.4  Slab-on-grade floors.  For slab-on-grade floors, the
  307. thermal resistance of the insulation around the perimeter of the
  308. floor shall not be less than the value given in Table 502.2.1a. 
  309. Insulation shall be placed on the outside of the foundation or on
  310. the inside of a foundation wall.   *>In climates below 6,000 annual
  311. Fahrenheit heating degree days (HDD) (Celsius) or greater,<*  The
  312. insulation shall extend downward from the top of the slab for  *>a
  313. minimum of 48 inches (1219 mm)<*  a minimum of 12 inches (304 mm)
  314. below grade, or to the bottom of the footing, whichever is greater;
  315. or downward to at least the bottom of the slab and then
  316. horizontally to the interior or exterior for a minimum total
  317. distance of  *>48 inches (1219 mm) <* 36 inches (914 mm).   *>In
  318. all climates,   t <* The horizontal insulation extending outside of
  319. the foundation shall be covered by pavement or by soil a minimum of
  320. 10 inches (254 mm) thick.  The top edge of the insulation installed
  321. between the exterior wall and the edge of the interior slab shall
  322. be permitted to be cut at a 45-degree angle away from the exterior
  323. wall.
  324.  
  325. Section 502.3.4  Recessed lighting fixtures.  Revise the first
  326. paragraph to read:
  327.  
  328. 503.2.4  Recessed lighting fixtures.  When installed in the
  329. building envelope, recessed lighting fixtures shall be constructed
  330. so as to accept only lamps with efficacy greater than 40
  331. lumens/watt, and meet one of the following requirements:
  332.  
  333. Section 503.2.1  Calculation procedures.  Add a sentence to read:
  334. Equipment not covered by the tables in this section shall show the
  335. following maximum installed cooling power densities, including all
  336. auxiliaries:
  337.  
  338.    less than 65,000 BTU/hr:   2.7 kW primary energy per 1000 sf at
  339.                               site
  340.    65,000 - 135,000 BTU/hr:        3.6 kW per 1000 sf
  341.    135,000 - 250,000 BTU/hr:       3.7 kW per 1000 sf
  342.    greater than 250,000 BTU/hr:    2.0 kW per 1000 sf
  343.  
  344. with energy intensity of mechanical cooling equipment calculated
  345. from EER ratings if entirely electric.
  346.  
  347. Table 503.35a Change the SEER values in the fourth column (Minimum
  348. Performance) from 10 and 9.7 to 12.0 and 10, respectively.
  349.  
  350. Section 503.4 Add a new sub-section to read:
  351.  
  352. 503.4.3 Speed Reduction: An automatic method of speed reduction for
  353. pump and fan motors, or air or water flow reduction, during less
  354. than full system load conditions, which assures energy savings
  355. through motor power input reduction, shall be employed for any air
  356. system that exceeds a total system static pressure of 2.0 inches
  357. water gauge, and any water system that exceeds a total water system
  358. pressure equivalent to a 50 foot head of water.
  359.  
  360. Section 503.5  Balancing.  Add a new second sentence to read:
  361. For structures with a floor area greater than 5000 square feet with
  362. forced-air climate control, balancing shall be performed, or
  363. included as part of a commissioning process from the design and
  364. construction phase.  Certification and results of the balancing
  365. shall be submitted to the jurisdiction, the owner and the designer
  366. of the project.
  367.  
  368. Section 503.9 Piping Insulation.  Delete exceptions 2 and 4, and
  369. renumber exception 3 to 2. 
  370.  
  371. Section 504.2  Water heaters, storage tanks and boilers.  Add a
  372. sentence to read:
  373.  
  374. All water heating applications which exceed a 30oF  T shall include
  375. a solar heating component, heat recovery from a device other than
  376. the water heater or an energy-equivalent alternative on a fuel use
  377. basis.
  378.  
  379. Section 504.2.1.1  Electric Water heaters.  Revise as follows:
  380.  
  381. 504.2.1.1  Electric Water heaters.  All Automatic electric storage
  382. water heaters  *>having a storage capacity of 120 gallons (454L) or
  383. less and an input rating of 12 kW or less <* shall have a standby
  384. loss not exceeding 4.0 watts/ft2 (43W/m2) of tank surface or 43
  385. watts, whichever is greater, when tested in accordance with
  386. Standard RS-5 listed in Chapter 8 and calculated at an 80o
  387. temperature difference. *>
  388. <* 
  389. Section 504.2.1.2 Gas- and oil-fired water heaters.
  390. Change the sixth paragraph to read:
  391. Natural gas-  *>and oil-<* fired water heaters  *>having an input
  392. rate of more than 4,000 Btu/h per gallon (1172 W per L) of stored
  393. water and having a pilot input rate greater than 0.5 percent of the
  394. maximum heater input rate (but not exceeding 750 Btu/h) (220 W)<* 
  395. shall be equipped with an ignition system which is not a
  396. continuously burning pilot light, and shall be accompanied by an
  397. automatic flue damper.
  398.  
  399. Section 504.2.3  Combination service water heating/space heating
  400. boilers.  Delete the exceptions.
  401.  
  402. Section 504.5.1  Add the following at the beginning of the
  403. paragraph:
  404. All recreational swimming pools shall utilize solar energy as the
  405. only water heating source.  Medical and rehabilitation pools
  406. smaller than 3,000 gallons water capacity shall use solar energy as
  407. the primary water heating source, with a new energy source
  408. permitted as backup.
  409.  
  410. Add a new Section 504.2.4: 
  411.  
  412. Section 504.5.4  Recirculating Systems.  Recirculating systems
  413. shall be provided with time clocks as required in Sec. 504.5.3,
  414. switches as required in Sec. 504.6, and pipe insulation as required
  415. in Sec. 504.7.
  416.  
  417. Section 504.8  Conservation of Hot Water.  Delete in its entirety
  418. and add "Plumbing fixtures supplied with hot water shall comply
  419. with Chapter 15 of the Tucson/Pima County Plumbing Code"
  420.  
  421. Add a new section 506 to read:
  422.  
  423. 506.  Energy Consumption - Other Than Electrical.
  424. In multifamily dwellings , provisions shall be made to determine
  425. the energy consumed by each tenant by separately metering
  426. individual dwelling units or tenant spaces.  
  427.  
  428.  
  429.                             CHAPTER 6
  430.         RESIDENTIAL BUILDING DESIGN BY ACCEPTABLE PRACTICE
  431.  
  432. Section 602.2.1  Walls.  Add the following paragraph to read:
  433.  
  434. 602.2.1.1  Wall assemblies.  Exterior walls shall be constructed to
  435. meet a minimum composite R-Value of 14 including air films.  The
  436. following assemblies are deemed to meet this requirement:
  437.  
  438. 1.   Nominal 2 x 6 wood-frame construction insulated with R-19
  439.      batts or loose-fill insulation.
  440. 2.   Nominal 2 x 4 wood-frame construction insulated with R-11
  441.      batts or loose-fill insulation and rigid insulation board on
  442.      the exterior with an R-Value of not less than 3.2, with a
  443.      nominal 4 inch brick veneer.
  444. 3.   Nominal 2 x 4 wood-frame construction insulated with R-11
  445.      batts or loose-fill insulation and rigid insulation board on
  446.      the exterior with an R-Value of not less than 5.0.
  447. 4.   Earthen material or solid masonry, with a total heat capacity
  448.      of 22 Btuh/ft/oF, at least 12 inches in thickness with rigid
  449.      insulation board with an R-Value of not less than 5.0 applied
  450.      to the exterior.
  451. 5.   Earthen material or solid masonry, with a total heat capacity
  452.      of 44 Btuh/ft/oF, at least 24 inches in thickness.
  453. 6.   Straw bales at least 14 inches in thickness.
  454. 7.   Log construction with an average thickness of 12 inches.
  455. 8.   Log construction with an average thickness of 6 inches and
  456.      nominal 2 x 4 frame construction insulated with R-11 batts or
  457.      loose-fill insulation.
  458.  
  459. Add the following exceptions after the last paragraph:
  460.  
  461. Exceptions:
  462. 1.   Doors whose area and U-value are considered as glazing in
  463.      section 602.2.1 shall be exempt.
  464. 2.   One exterior swinging door with a maximum area of 32 square
  465.      feet may be installed for ornamental, security or
  466.      architectural purposes and be exempt from these requirements.
  467.  
  468. Add new subsections to read:
  469.  
  470. 602.2.1.1  Exterior door area.  For doors containing at least 20
  471. percent of the door area in glazing, the glazing area shall be
  472. subtracted from the door area for the purpose of determining the U-value of the door.
  473.  
  474. 602.2.1.2  Exterior door U-value.  All exterior doors shall have a
  475. maximum area weighted U-value not exceeding that prescribed in
  476. Table 102.3b.
  477.  
  478. 602.2.1.3  Glazing.  Whole-unit glazing maximum U-value shall be
  479. determined by the following equation:
  480.  
  481.      U =  5 / ((Glazing Percentage) - 5)
  482.  
  483. where Glazing Percentage = 100 x (glazing area  /  floor area)
  484.  
  485. Section 602.2.2  Roof/ceiling.  Add a new subsection to read:
  486.  
  487. 602.2.2.1 Roof/ceiling assemblies.  Ceilings below ventilated attic
  488. spaces and single rafter vaulted ceilings shall be constructed to
  489. meet a minimum composite R-value of 38 including air films.
  490.   The following assemblies are deemed to meet this requirement:
  491.  
  492. 1.   Wood-frame assembly insulated with R-36 batts or loose-fill
  493.      insulation.
  494. 2.   Earthen material or solid masonry, with a total heat capacity
  495.      of 22 Btuh/ft/oF, at least 12 inches in thickness with glass
  496.      fiber or foam insulation with an R-Value of not less than 22
  497.      applied to the interior.
  498. 3.   Earthen material or solid masonry, with a total heat capacity
  499.      of 44 Btuh/ft/oF, at least 24 inches in thickness with glass
  500.      fiber or foam insulation with an R-Value of not less than 11
  501.      applied to the interior.
  502. 4.   Earthen material or solid masonry, with a total heat capacity
  503.      of 66 Btuh/ft/oF, at least 36 inches in thickness
  504. 5.   Straw bales at least 14 inches in thickness.
  505.  
  506. Section 602.2.4 Slab-on-grade floors.
  507.  
  508. Change the second paragraph as follows:
  509. Insulation shall be placed on the outside of the foundation or on
  510. the inside of a foundation wall.   *>In climates below 6,000 annual
  511. Fahrenheit heating degree days (HDD) (Celsius) or greater,<*  The
  512. insulation shall extend downward from the top of the slab for  *>a
  513. minimum of 48 inches (1219 mm)<*  a minimum of 12 inches (304 mm)
  514. below grade to, or the bottom of the footing which ever is greater;
  515. or downward to at least the bottom of the slab and then
  516. horizontally to the interior or exterior for a minimum total
  517. distance of  *>48 inches (1219 mm) <* 36 inches (914 mm).   *>In
  518. all climates, t <*  The horizontal insulation extending outside of
  519. the foundation shall be covered by pavement or by soil a minimum of
  520. 10 inches (254 mm) thick.  The top edge of the insulation installed
  521. between the exterior wall and the edge of the interior slab shall
  522. be permitted to be cut at a 45-degree angle away from the exterior
  523. wall.  At least 25 percent of the floor area in the living space
  524. shall be without carpet.
  525.  
  526. Section 603.2 HVAC equipment requirements, change to read:  ...
  527. efficiency and power density requirements of section 503.2 and
  528. 503.3. 
  529.  
  530. Table No. 603.5  Minimum Pipe Insulation;  Revise by changing the
  531. numbers 1 1/2 to 1/2 in the third and fourth columns on the line
  532. "CHILLED WATER".
  533.  
  534. Section 603.6  Add a new section to read:
  535.  
  536. 603.6  Space Cooling.  Buildings that are cooled using air
  537. conditioners or air-to-air, ground-to-air or water-to-air heat
  538. pumps shall be sized to provide a ratio of one ton of cooling per
  539. 600 square feet or more of floor space.  System sizing shall be
  540. determined by an analysis consistent with industry standards.
  541.  
  542. Section 603.7  Add a new subsection to read:
  543.  
  544. 603.7  Mechanical Equipment and Water Heater Efficiency.  The
  545. efficiency of water heating and mechanical equipment shall be in
  546. accordance with sections 503 and 504 of this code.
  547.  
  548.                            SECTION 604
  549.                       SERVICE WATER HEATING
  550.  
  551. Section 604.1.2.3  Swimming Pools.  Add the following at the
  552. beginning of the first paragraph:
  553. All recreational swimming pools shall utilize solar energy as the
  554. only water heating source.  Medical and rehabilitation pools
  555. smaller than 3,000 gallons water capacity shall use solar energy as
  556. the primary water heating source, with a new energy source
  557. permitted as backup.  When permitted,  *>P<* pool . . . . .
  558. remainder unchanged.
  559.  
  560. Section 604.4  Conservation of hot water.  Delete in its entirety
  561. and add "Plumbing fixtures supplied with hot water shall comply
  562. with Chapter 15 of the Tucson/Pima County Plumbing Code"
  563.  
  564.                             CHAPTER 7
  565.            BUILDING DESIGN FOR ALL BUILDINGS OTHER THAN
  566.                       RESIDENTIAL BUILDINGS
  567.  
  568. Section 702.1  Basic Requirements.  Revise to read as follows:
  569.  
  570. 702.1  Basic Requirements.  Building designs shall meet the
  571. requirements of Chapter 4, 5 or 6 of this code as well as the
  572. requirements of Sections 5.4, 6.4, 7.4, 8.4, 9.4, 10.4, 11.4 and
  573. 12.4 in Standard RS-22 listed in Chapter 8.
  574.  
  575. Section 702.2  Additional requirements.  Add the following before
  576. the first exception:
  577. Buildings otherwise meeting the requirements of Chapter 4, 5 or 6
  578. of this code may employ the following performance requirement
  579. substitutions of Standard RS-22, listed in Chapter 8:
  580. Remainder unchanged.
  581.  
  582. Add a new section to read:
  583.  
  584.                            SECTION 703
  585.                      ELECTRICAL REQUIREMENTS
  586.  
  587. 703.1 Lighting Power Budget.   The maximum lighting power density
  588. (LPD) for any building may be calculated by either the Complete
  589. Building Method or the Area Category Method, according to the
  590. following table:
  591.  
  592.  
  593.  
  594.  
  595.  
  596.                            TABLE 703.1
  597.                      Complete Building Method
  598. Building Type                      Max.Lighting Power Density
  599.                                                    (W/sf)
  600.  
  601. General commercial or industrial work buildings   0.8
  602. Grocery stores                                    1.2
  603. Industrial or commercial storage buildings        0.5
  604. Medical buildings and clinics                     1.0
  605. Office buildings                                  1.0
  606. Religious worship, auditorium/convention centers  1.3
  607. Restaurants                                       1.0
  608. Retail and wholesale stores                       1.3
  609. Schools                                           1.2
  610. Theaters                                          1.0
  611. All others                                        0.5
  612.                                 
  613.                        Area Category Method
  614. Area Type                          Max.Lighting Power Density
  615.                                                   (W/sf)
  616.  
  617. Auditorium                                        1.3
  618. Bank/financial institutions                       1.2
  619. Classrooms                                        1.3
  620. Convention/conference/meeting centers             1.0
  621. Corridors, restrooms, support areas               0.5
  622. Dining                                            0.8
  623. Exhibit                                           1.5
  624. General commercial and industrial work            0.8
  625. Grocery                                           1.3
  626. Hotel function                                    1.5
  627. Industrial and commercial storage                 0.4
  628. Kitchen                                           1.5
  629. Lobbies:  Hotel lobby                             1.5
  630.           Main entry lobby                        1.0
  631. Malls, arcades, and atria                         0.8
  632. Medical and clinical care                         1.2
  633. Office                                            1.0
  634. Precision commercial and/or industrial work       1.3
  635. Religious worship                                 1.4
  636. Retail sales, wholesale showrooms                 1.4
  637. Theaters:  Motion picture                         0.7
  638.                Performance                        1.0
  639.  
  640. For any building greater than 5,000 square feet in area, and for
  641. all non-residential buildings, the following shall apply:
  642. Lighting design shall comply with current IESNA guidelines and
  643. application notes, with selection of the median illuminance as
  644. the target optimum, not the minimum.  In all areas designated
  645. higher than IESNA category C, specified illuminance shall be on
  646. task, with ambient illuminance generally task/3.  LPD shall in no
  647. case exceed the values in Table 703.1.  In all areas, lighting
  648. targets shall be achieved by the most energy efficient technology
  649. which meets the following requirements:
  650.  
  651.   └"└CRI greater than 80 for work areas, greater than 75 for all
  652.   areas.
  653.   └"└Color Temperature less than 3600oK, except in retail display,
  654.   excluding tasklights
  655.  
  656. Technologies include but are not limited to:
  657.   └"└Incorporation of natural daylight, and daylight-supplementing
  658.   artificial light
  659.   └"└Area lighting by high-CRI straight tube fluorescent with
  660.   specular reflectorized interior luminaire.  Fully electronic
  661.   instant start 4-lamp parallel-circuit ballasts, wired in
  662.   tandem to multiple luminaries.  Daylight-dimming via photocell
  663.   sensor/controller.
  664.   └"└Task lighting by 13 watt lamps (or smaller), with laterally
  665.   offset placement so as not to cause direct or veiling glare
  666.   └"└Conference rooms to have continuous architectural-dimming (to
  667.   10%) fluorescent luminaries in place of can downlights, or
  668.   else can lights controlled by center-off double throw switch
  669.   which prevents simultaneous operation of area lights and
  670.   downlights.
  671.  
  672. Prohibited technologies include:
  673.   └"└Tungsten filament incandescent except quartz-halogen
  674.   └"└T12 fluorescent
  675.   └"└VHO and SHO lamps
  676.   └"└Mercury vapor lamps
  677.   └"└U-shaped lamps (except CFLs <20W)
  678.   └"└Small-cell paracube grates
  679.   └"└Magnetic fluorescent ballasts
  680.   └"└Series-circuit ballasts
  681.   └"└Unreflectorized interior luminaries
  682.  
  683. Occupancy Sensors shall be specified and installed in accordance
  684. with EPA Green Lights guidelines, with control technology
  685. appropriate to the application.  
  686. Areas with video display terminals shall be primarily illuminated
  687. by task lighting, with overhead luminaries using high-VCP
  688. transparent lenses.  Visual acuity factors are to be treated as
  689. minus weighting factors.
  690. Areas with visible daylight shall use continuous-dimming
  691. photocell-controlled variable light output devices except those
  692. controlled by non-defeatable occupancy sensors.  Daylighting
  693. contribution to be considered in calculation of IESNA target
  694. illuminance.